Limits of the Current Harmonics  according to EN 61000-3-2/VDE 0838 Part 2

Class A: Symmetrical three-phase appliances and all other appliances, which are not referred in one of the other classes

Class B: Portable electric power tools

Class C: Lighting equipment inclusively dimmers

Class D: After the modification EN 61000-3-2/A14 the validity of the class D is limited to TV and broadcast receivers , PCs and monitors

The limits do not apply to a nominal input power of less than 75W (except for lighting equipment) and to dimmers with a input power of less than 1 kW.

Note: Limits values for professional devices with more than 1 KW of capacity still are in consultation

Limits

 Order of harmonic n

 Class A

 A

 Class B

 A

 Class C

 I n /I 1 in %

 Class D

 mA/W

 Odd harmonics





 3

 2,3

 3,45

 30 * l

 3,4

 5

 1,14

 1,71

 10

 1,9

 7

 0,77

 1,16

 7

 1

 9

 0,4

 0,6

 5

 0,5

 11

 0,33

 0,5

 3

 0,35

 13

 0,21

 0,32

 3

 0,3

 15 - 39

 0,15 * 15/n

 0,225*15/n

 3

 3,85/n

 Even harmonics





 2

 1,08

 1,62

 2


 4

 0,43

 0,65



 6

 0,3

 0,45



 8 - 40

 0,23*8/n

 0,35*8/n



 After the modification EN61000-3-2/A14 with variable load the average values of the harmonics should not exceed the limit values